Lightning & Surge Protection |
|
POWER PROTECTION |
| |
PRIME-PRO

Features PRIME PRO
The Prime-Pro40/280 and 100/280 is designed for the primary (coarse) protection of mains supplies. It will dissipate extremely severe lightning-induced transients of up to 40 000 Amps. Suitable for DIN rail mounting in mains distribution boards. The unit should be connected in parallel between each conductor to be protected, and earth. Each module incorporates mechanical flag failure indication.
* Designed for DIN rail mounting
* Powerful but compact
Compliance Prime-Pro Terminals Layout
* SABS0171
* Escom NWS1108
* IEC 1312-3 for LPZOB
* IEC 61643-1 : 1998
Electrical Specifications
Static Conditions @ 25°C
Mains Max continuous voltage (per phase) 280V rms (350V DC)
Typical earth leakage current (per phase) <1mA
Operating temperature -10° to +55°C
Typical capacitance 2700pF
Transient Conditions @ 25°C
Mains Max voltage withstand (1.2/50µs) >10kV
Max current withstand (8/20µs) 8 / 15 / 40 / 100kA
Max energy withstand (2ms) 550 joules (40kA) 1320 joules (100kA)
Max clamping voltage 710V
Typical response time <25ns
Stock Numbers
10-402 : 40kA
10-500 : 40kA
10-102 : 100kA
Indoor with functional/defective indication
10-082 : 8kA
10-152 : 15kA
10-402 : 40kA
10-102 : 100kA
Indoor without indication
10-080 : 8kA
10-015 : 15kA
10-040 : 40kA
10-100 : 100kA
Indoor with annunciator
10-815 : 8kA
10-840 : 15kA
10-888 : 40kA
10-999 : 100kA
|
|
HC-PRO SUPER

Features HC-Pro Super
These high-current, single and three phase suppressors/filters are available for continuous current ratings of up to 120A rms per phase. They are supplied in wall mounting enclosures and are fitted with replaceable primary (40kA and 100kA) and secondary transient suppression modules.
*Terminal contact available on primary protection surge arrestors for alarm monitoring
*Ideal for protection of medical CAT or MRI scanners etc
*To be used for the centralised protection of computer rooms
*Powerful filtration with 40 or 100kA suppression
*Replaceable transient suppression modules
Electrical Specifications
Static Conditions @ 25°C
Mains Max continuous voltage (per phase) 250V rms
Max continuous current (per phase) 60/90/120A...2000A
Typical earth leakage current (per phase) <2mA
Operating temperature -10° to +55°C
Transient Conditions @ 25°C (Primary)
Mains Max voltage withstand per cond. (1.2/50µs) >10kV
Max current withstand per cond. (8/20µs) >40/100kA
Max energy withstand per cond. (2ms) 550/1320J
Typical clamping voltage 710V
Typical response time <25ns
Transient Conditions @ 25°C (Secondary)
Mains Max voltage withstand (1.2/50µs) >6kV
Max current withstand (8/20µs) >6kA
Max energy withstand (2ms) 140J
Peak EMI/RFI noise attenuation (Approx) 60dB
Typical clamping voltage 570V
Stock Numbers
L W H Weight
11-160 60A Single phase 400 300 210 15Kg
11-190 90A Single phase 550 400 210 18Kg
11-112 120A Single phase 550 400 210 18Kg
11-360 60A Three phase 550 400 210 20Kg
11-390 90A Three phase 700 500 265 27Kg
11-312 120A Three phase 700 500 265 29Kg
Note:
Timer options available |
| |
POWER-PRO SUPREME GRADE

Features Power-Pro Supreme Grade
The Power-Pro Supreme Grade mains transient suppressor and EMI/RFI filter module is a high-perfomance device which is designed to afford ultimate protection to sensitive electronic and electrical equipment against damaging mains-borne transients and interference.
* High Performance filter circuit
* Simple plug-in installation
*110/115 volt models available upon request
*Also available in a 'feed-through' configuration for direct cabling
*Current ratings of either 5, 10, 15, 20 or 30 Amps
*Most standard international plugs and sockets available Compliance
*IEC 99-4
*BS EN60950
*AS 1307-2
*AS 1768
*AS 1931-1
Electrical Specifications
Static Conditions @ 25°C Mains
Max continuous voltage 250V rms
Max continuous current (110/115V models available on request)
5, 10, 15, 20 or 30A
Typical earth leakage current <2mA
Operating temperature –10° to +55°C
Transient Conditions @ 25°C (Primary) Mains
Max voltage withstand (1.2/50µs) >6kV
Max current withstand (8/20µs) >6kA
Max energy withstand (per wire) 140 Joules
Peak EMI/RFI noise attenuation (Approx.)100dB
Max clamping voltage 570V
Stock Numbers
12-050 : Power-Pro 5 Amp Supreme Grade feed-through
12-056 : Power-Pro 5 Amp Supreme Grade with 16 Amp plug and socket
12-059 : Power-Pro 15 Amp Heavy Duty feed-through
12-100 : Power-Pro 10 Amp Supreme Grade feed-through
12-106 : Power-Pro 10 Amp Supreme Grade with 16 Amp plug and socket
12-150 : Power-Pro 15 Amp Supreme Grade feed-through
12-156 : Power-Pro 15 Amp Supreme Grade with 16 Amp plug and socket
12-159 : Power-Pro 15 Amp Heavy Duty with 16 Amp plug and socket
12-200 : Power-Pro 20 Amp Supreme Grade feed-through
12-300 : Power-Pro 30 Amp Supreme Grade feed-through
Note:
i) 20 and 30 Amp units available in “feed-through” version only.
ii) For international versions of above products please add country abbreviation to the required stock number, eg: 12-100UK or 12-100AUS.
iii) The above units are also available with coded sockets.
iv) Other variations available on request
EQUI-PRO

Features Equi-Pro
The Equi-Pro is designed to suppress noise contamination of dedicated earthing systems for electronic equipment and, at the same time, maintain equal potentials between these systems and the raw mains earth.
Both these factors are critical to prevent malfunctions and damage occuring to sensitive instrumentation and control equipment, particularly those located in industrial environments. A further feature incorporated into the Equi-Pro is that, should there be a sudden and serious potential rise in one of the earthing systems, due perhaps to a nearby lightning strike, this will immediately activate a device which bypasses the circuitry, thereby ensuring a low impedance path between the systems for the duration of the
overvoltage.
Electrical Specifications
Static Conditions @ 25°C
Max DC resistance <1 0hm
Max continuous current 5A
Noise Attenuation @50Hz 17dB @10Hz 64dB @200Hz108dB @10MHz 570dB
Operating temperature -10° to +80°C
Transient Conditions @ 25°C
Max current withstand (8/20µs) >5kA
Typical clamping voltage 110V
Typical response time 25ns
Stock Number 27-000
|
|
PRIME-PRO OUTDOOR RANGE

Features Prime-Pro Outdoor Range
The Prime-Pro Outdoor Range is designed for the primary (coarse) protection of mains supplies. These modules are suitable for external or internal mounting and afford economical but powerful protection against severe lightning-induced transient overvoltages. The Prime-Pro Outdoor Range should be connected in parallel between each conductor to be protected, and earth. The range is available in single, double and four pole formats. Other voltage ratings are available on request.
*Designed for external use
*Powerful but compact
Compliance
*SABS0171
*Escom NWS 1108
*IEC 1312-3 for LPZOB
*IEC 61643-1 : 1998
Electrical Specifications
Static Conditions @ 25°C Mains
Max continuous voltage (per phase) 275V (350V DC)
Typical earth leakage current (per phase) <1mA
Operating temperature -40° to +85°C
Transient Conditions @ 25°C Mains
Max continuous voltage (1.2/50µs) >10kV
Max current withstand (8/20µs) 10/40/100kA
Typical clamping voltage (@300A) 710V
Typical response time <25ns
Stock Numbers
10-013 : Poles: Single + E To Protect: L or N 1(max/cond): 10kA (8/20µs)
10-043 : Poles: Single + E To Protect: L or N 1(max/cond): 40kA (8/20µs)
10-103 : Poles: Single + E To Protect: L or N 1(max/cond): 100kA (8/20µs)
PLC-PRO

Features PLC-Pro
This DIN rail mounting system offers compact, powerful and economical protection for multiple low-voltage conductor pairs. The 10kA rated mini plug-in modules can be simply replaced without disconnecting the equipment circuitry. Each module protects one conductor pair and the base section is sized to suit the number of modules required per system.
*No disconnection of equipment when changing modules
*Economical and compact design
*Fully-graded protection per module
*Wide range of applications
Range
Low-Voltage Protection
PLC-PR
The PLC-PR offers excellent common and differential mode suppression characteristics. It is designed for use with semi-floating, low to medium frequency circuits (up to 20kHz) which carry currents up to 450mA at a range of voltages from 5 to 48 Volts DC (3 to 32 Volts AC rms 50Hz). Typical applications for this device would be loop powered instrumentation and 4 – 20mA signals.
PLC-PL
This unit has similar suppression characteristics to the PLC-PL, but is designed for use with semi-floating DC or low frequency circuits (up to 10kHz). It has a lower DC series impedance and can handle steady state currents up to 1Amp. A typical application for this range of devices would be semi floating DC power supplies.
Stock Numbers
28-XX/YY : Resistive circuit
28-XX/YY/S : Spare module
29-XX/YY : Inductive circuit
29-XX/YY/S : Spare module
XX - indicates the number of protected pairs required
YY - indicates voltage required
|
| |
CER-PRO

Features Cer-Pro
The Cer-Pro isolates spark gap against direct lightning strokes.
Applications
Isolation of earthings
*Isolation of earthings for cathodically protected tanks
*Isolation of signal and building earths
When overvoltages occure the isolating spark gap connect earths which normally must be separated. The appearance of inadmissible potential differences is thus avoided and the lightning current is discharged to earth without causing any damage.
*Surge protection for aerials
*Surge protection for other systems, for example emergency telephone stations, exposed to direct lightning
Technical Features
min normal max
d.c. sparkover voltage
UZstat V 80, 100, 120
a.c. sparkover voltage V 56, 70, 84
impulse sparkover voltage (1kV/µs)
(before subject to heavy surge currents)
UZdyn V 680, 900
discharge rating according to DIN 48810
(20 loads 10/45 and 1.6kA with sine half-wave of 10ms)
kA 60
discharge rating according to VDE 0845
(10 loads in the form 6/20) kA 100
Insulation resistance Ris Ω 109
Stock Number
27-001
|
|
SURGE CORD

Features Surge Cord
The Surge Cord offers both transient suppression and EMI/RFI filtration. The housing may be plugged directly into a standard 16 Amp round pin socket outlet and may be connected to equipment by means of standard IEC type connector. It is an ideal product for use in the protection of electrical/electronic equipment.
* Compact and inexpensive
*Simple plug-in installation
*Full transient suppression on all conductors
*Incorporates powerful filtration circuitry
The Surge Cord is available in all international variants ie: UK, Australian, Italian etc.
Compliance
*IEC 99-4
Electrical Specifications
Static Conditions @ 25°C Mains
Max continuous voltage (110/115V models available on request)250V
Max continuous current 10A
Typical earth leakage current <2mA
Operating temperature –10° to +55°C
Transient Conditions @ 25°C Mains
Max voltage withstand (1.2/50µs) >6kV
Max current withstand (8/20µs) >6kA
Max energy withstand (per wire) 140 Joules
Peak EMI/RFI noise attenuation (Approx.) 45dB
Typical clamping voltage 570V
Typical response time <25ns
Stock Numbers
16-104
16-104 : UK/Aus/It
Note:
Available in Black/Grey |
|