COMLEC 

Home Products About Us  Technologies Site Map Contact us

 

 

QUALITY AND TECHNOLOGY
 

 

Transformers
DC power supply
Voltage Stabilisers
Inductors and Harmonic Filters
Special Products

RTFX - three phase inductor for capacitor banks

Inductor for application in capacitor banks

copper windings, low temperature rise

Products in this family
Reference Capacitor Rating kvar Effective Rating kvar Current (A)
RTFX 5 5 kvar / 440V 4,4 kvar 6,8 A
RTFX 10 10 kvar / 440V 8,9 kvar 13,6 A
RTFX 12,5 12,5 kvar / 440V 11,1 kvar 17,0 A
RTFX 15 15 kvar / 440V 13,3 kvar 20,4 A
RTFX 20 20 kvar / 440V 17,8 kvar 27,2 A
RTFX 25 25 kvar / 440V 22,2 kvar 34,0 A
RTFX 30 30 kvar / 440V 26,7 kvar 40,8 A
RTFX 40 40 kvar / 440V 35,5 kvar 54,4 A
RTFX 50 50 kvar / 440V 44,4 kvar 68 A
RTFX 60 60 kvar / 440V 53,3 kvar 82 A
RTFX 80 80 kvar / 440V 71,1 kvar 109 A
RTFX 100 100 kvar / 440V 88,8 kvar 136 A
 

 

Measurements and weights
Reference Capacitor Rating kvar Dimensions mm Weight kg Fig.
A B C D E Ű
RTFX 5 5 kvar / 440V 150 111 180 85 100 6 4.60
RTFX 10 10 kvar / 440V 150 126 180 100 100 6 7.60
RTFX 12,5 12,5 kvar / 440V 150 141 180 115 100 6 9.50
RTFX 15 15 kvar / 440V 180 126 215 100 120 6 11.10
RTFX 20 20 kvar / 440V 180 131 215 120 105 6 12.10
RTFX 25 25 kvar / 440V 180 141 215 115 120 6 14.00
RTFX 30 30 kvar / 440V 180 156 215 130 120 6 16.80
RTFX 40 40 kvar / 440V 180 176 215 150 120 6 20.90
RTFX 50 50 kvar / 440V 180 186 215 160 120 9 22.90
RTFX 60 60 kvar / 440V 180 201 215 175 120 9 25.80
RTFX 80 80 kvar / 440V 240 161 285 135 160 9 33.20
RTFX 100 100 kvar / 440V 240 186 285 160 160 9 40.80

Technical Characteristics
Frequencies  50 Hz
Isolation  Class F - 155șC
Winding  Class HC-200șC
Test voltage  3 kV (1 min, 50 Hz)
Protection degree  IP-00
Standards  IEC/EN/UNE-EN 60289 CE
Includes  Thermal protection against over temperature
Ambient temperature  45șC
Temperature rise  < 85 șC
Thermal overload factor  5 %
Line voltage  400 V
Resonance frequency  189 Hz (P = 7 %)
Capacitor voltage  440 V
Harmonic currents  I3 = 8 %, I5 = 31 %, I7 = 13 %
Over current In  6 %
Inductance tolerance  +/- 3 %
- Avoids resonance between the inductance of the supply transformer and the capacity of the capacitor bank
- Eliminates over voltage and over current in the transformer and the capacitor bank
- Protects capacitors against harmonics, avoiding premature breakdown of the capacitor bank
- Limits the connection spikes of he capacitor bank, extending its lifetime and reducing microcuts in the voltage

Inductors and Harmonic filters  

 
RTFX - three phase inductor for capacitor banks  
RTLX - three phase line inductor
RTL - three phase Cast Resin line inductor
RTOX - three phase inductor for output power converter
FTOX - output filter for power converters
PR - single phase line inductor
R - single phase Cast Resin line inductor 
CD - harmonic filter Compensator for office buildings C10D and C20D 
CD - harmonic filter Compensator for office buildings C10D and C22D
CD - harmonic filter Compensator for office buildings C25D-0 and C25D-180, with galvanic isolation
CD - harmonic filter Compensator for office buildings C30D, with galvanic isolation
CF - harmonic filter Compensator for industrial instalations C10F
CF - harmonic filter Compensator for industrial instalations C20F, with galvanic isolation
 

 

 

Transformers
DC power supply
Voltage stabilizers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Home

Products and Services  Corporate Structure  Technologies Site Map Contact us

                      COMLEC PTE LTD    The SkyTech. Blk 2 #05-11 Bukit Batok Street 24. Singapore 659480  Tel:65-67415738  Fax:65-67444696  

                                                                       Email: comlec@pacific.net.sg  or  sales@comlec.com

                        ©copyright 2001~2009 Comlec Pte Ltd. All rights reserved. Disclaimer                        updated 25 Apr 2010