| Line inductor for harmonic filtering
| Products in this
family |
| Reference |
In(A) |
Motor
rating |
L(mH) |
| PR
2,5 |
2,5
A |
0,23
kW / 0,31 CV |
8,785 |
| PR 4 |
4 A |
0,38
kW / 0,5 CV |
5,491 |
| PR 5 |
5 A |
0,46
kW / 0,6 CV |
4,393 |
| PR
6,3 |
6,3
A |
0,55
kW / 0,75 CV |
3,486 |
| PR 8 |
8 A |
0,75
kW / 1 CV |
2,745 |
| PR
10 |
10 A |
1,1
kW / 1,5 CV |
2,196 |
| PR
12,5 |
12,5
A |
1,5
kW / 2 CV |
1,757 |
| PR
16 |
16 A |
1,85
kW / 2,5 CV |
1,373 |
| PR
20 |
20 A |
2,2
kW / 3 CV |
1,098 |
| PR
25 |
25 A |
3 kW
/ 4 CV |
0,879 |
| PR
31,5 |
31,5
A |
4 kW
/ 5,5 CV |
0,697 |
|
| Measurements and
weights |
|
| Reference |
In(A) |
Dimensions
mm |
Weight
kg |
Fig. |
| A |
B |
C |
D |
E |
Ø |
| PR
2,5 |
2,5
A |
84 |
101 |
98 |
88 |
55 |
5 |
0.74 |
|
| PR 4 |
4 A |
84 |
101 |
98 |
88 |
55 |
5 |
0.74 |
|
| PR 5 |
5 A |
84 |
101 |
98 |
88 |
55 |
5 |
0.90 |
|
| PR
6,3 |
6,3
A |
106 |
123 |
118 |
110 |
74 |
5 |
1.30 |
|
| PR 8 |
8 A |
106 |
123 |
118 |
110 |
74 |
5 |
1.30 |
|
| PR
10 |
10 A |
106 |
123 |
118 |
110 |
74 |
5 |
1.30 |
|
| PR
12,5 |
12,5
A |
106 |
123 |
118 |
110 |
74 |
5 |
1.30 |
|
| PR
16 |
16 A |
106 |
123 |
118 |
110 |
74 |
5 |
1.80 |
|
| PR
20 |
20 A |
118 |
138 |
131 |
121 |
88 |
6 |
3.10 |
|
| PR
25 |
25 A |
118 |
138 |
131 |
121 |
88 |
6 |
3.10 |
|
| PR
31,5 |
31,5
A |
136 |
162 |
156 |
145 |
104 |
6 |
3.10 |
|
| Technical
Characteristics |
| Frequencies |
50-60 Hz |
| Isolation |
Class B - 130ºC |
| Winding |
Class HC-200ºC |
| Test voltage |
3 kV (1 min, 50 Hz) |
| Mounting |
Din Rail mounting (for all ratings) |
| |
By screws (for all ratings) |
| Cover |
Polymer of latest technology,
non-flammable V-0 according to UL94 |
| Protection degree |
IP-20 |
| Standards |
IEC/EN/UNE-EN 60289 CE |
| Includes |
Thermal protection against over
temperature |
| Line voltage |
220 - 260 V |
Voltage drop: 3%
- Reduction of current harmonics generated by the load,
resulting in reduced energy consumption and power factor
improvement
- Reduction of the crest factor of the current wave,
extending the lifetime of the equipment and avoiding
breakdowns
- Attenuation of microcuts in the supply voltage generated
by power converters, causing malfuntioning of computers,
PLC's and other sensitive equipment
|
|