COMLEC 

Home Products About Us  Technologies Site Map Contact us

 

 

QUALITY AND TECHNOLOGY
 

 

Transformers
DC power supply
Voltage Stabilisers
Inductors and Harmonic Filters
Special Products

FTOX - output filter for power converters

Products in this family
Reference In (A) L (mH) Volt. drop
FTOX 2.5 2,5 A 8,821 3 %
FTOX 4 4 A 5,513 3 %
FTOX 5 5 A 4,411 3 %
FTOX 6.3 6,3 A 3,501 3 %
FTOX 8 8 A 2,757 3 %
FTOX 10 10 A 2,205 3 %
FTOX 12.5 12,5 A 1,764 3 %
FTOX 16 16 A 1,378 3 %
FTOX 20 20 A 1,103 3 %
FTOX 25 25 A 0,882 3 %
FTOX 31.5 31,5 A 0,700 3 %
FTOX 40 40 A 0,551 3 %
FTOX 50 50 A 0,441 3 %
FTOX 63 63 A 0,350 3 %
FTOX 80 80 A 0,276 3 %
FTOX 100 100 A 0,221 3 %
FTOX 125 125 A 0,176 3 %
FTOX 160 160 A 0,138 3 %
FTOX 200 200 A 0,110 3 %
FTOX 250 250 A 0,088 3 %
FTOX 315 315 A 0,070 3 %
FTOX 400 400 A 0,055 3 %
FTOX 500 500 A 0,044 3 %
FTOX 630 630 A 0,035 3 %
Measurements and weights
Reference In (A) Dimensions mm Weight kg Fig.
A B C D E Ø
FTOX 2.5 2,5 A 150 153 180 48 100 9 2.50
FTOX 4 4 A 150 163 180 48 100 9 3.70
FTOX 5 5 A 150 163 180 58 100 9 3.80
FTOX 6.3 6,3 A 150 163 180 58 100 9 3.90
FTOX 8 8 A 150 168 180 63 100 9 4.50
FTOX 10 10 A 150 173 180 68 100 9 5.20
FTOX 12.5 12,5 A 150 178 180 73 100 9 5.90
FTOX 16 16 A 150 183 180 78 100 9 6.80
FTOX 20 20 A 150 193 180 88 100 9 8.30
FTOX 25 25 A 150 198 180 93 100 9 9.00
FTOX 31.5 31,5 A 180 193 215 88 120 9 11.60
FTOX 40 40 A 180 208 215 103 120 9 14.40
FTOX 50 50 A 180 223 215 118 120 9 17.20
FTOX 63 63 A 180 248 215 143 120 9 21.80
FTOX 80 80 A 240 223 285 118 160 9 29.40
FTOX 100 100 A 240 233 285 128 160 9 32.90
FTOX 125 125 A 240 258 285 153 160 9 41.10
FTOX 160 160 A 300 208 355 103 200 9 39.20
FTOX 200 200 A 300 228 355 123 200 9 49.60
FTOX 250 250 A 300 248 355 143 200 9 60.00
FTOX 315 315 A 300 283 355 178 200 9 77.00
FTOX 400 400 A 300 308 355 203 200 9 93.00
FTOX 500 500 A 360 308 425 203 240 11 132.00
FTOX 630 630 A 360 348 425 243 240 11 160.00

Technical Characteristics
Test voltage  3 kV (1 min, 50 Hz)
Protection degree  IP-00
Includes  Thermal protection against over temperature
Ambient temperature  40ºC
Temperature rise  < 90 ºC
Thermal class  F
Thermal overload factor  5 %
Line voltage  400 V
Remarks  Maximum output voltage 2Un (800V)
Attenuation of voltage spikes at the output of the power converter; these spikes cause deterioration of the motor isolation.
Elimination of the reflection effect due to long cable lengths between converter and motor. This reflection amplifies the voltage at the motor terminals.
These inductors are recommended for cable lengths of 50m or more between power converter and motor.

 

Inductors and Harmonic filters  

 
RTFX - three phase inductor for capacitor banks  
RTLX - three phase line inductor
RTL - three phase Cast Resin line inductor
RTOX - three phase inductor for output power converter
FTOX - output filter for power converters
PR - single phase line inductor
R - single phase Cast Resin line inductor 
CD - harmonic filter Compensator for office buildings C10D and C20D 
CD - harmonic filter Compensator for office buildings C10D and C22D
CD - harmonic filter Compensator for office buildings C25D-0 and C25D-180, with galvanic isolation
CD - harmonic filter Compensator for office buildings C30D, with galvanic isolation
CF - harmonic filter Compensator for industrial instalations C10F
CF - harmonic filter Compensator for industrial instalations C20F, with galvanic isolation

 

 

Transformers

 

DC power supply

 

Voltage stabilizers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

Home

Products and Services  Corporate Structure  Technologies Site Map Contact us

                      COMLEC PTE LTD    The SkyTech. Blk 2 #05-11 Bukit Batok Street 24. Singapore 659480  Tel:65-67415738  Fax:65-67444696  

                                                                       Email: comlec@pacific.net.sg  or  sales@comlec.com

                        ©copyright 2001~2009 Comlec Pte Ltd. All rights reserved. Disclaimer                        updated 25 Apr 2010