COMLEC 

Home Products About Us  Technologies Site Map Contact us

 

 

Intelligence-Embedded Devices... more than Protection Relays

 

 

 

 

 

 

 

 

 

 

 
Application
The relay type NA20 is typically used in HV, MV and LV radial networks as feeder or power transformer protection.
In solidly grounded systems the residual overcurrent protection can be used on feeders of any lenght, while in ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be used on feeders of small lenght in order to avoid unwanted trippings due to the capacitive current contribution of the feeder on external ground fault.
Beside to the phase and residual overcurrent protection, the following protective functions are provided:
- thermal image protection of lines and power transformers,
- undercurrent protection for monitoring of CB opening,
- negative sequence protection against asymmetrical short circuits and unbalance loads,
- I2/I1 protection against phase interruption under low-load condition.

Protective functions
50/51 - Phase overcurrent
50N/51N - Residual overcurrent
49 - Thermal image
37 - Undercurrent
46 - Negative-sequence overcurrent
I2/I1 - Phase interruption under low-load condition
BF - Circuit breaker failure
 
   

Home

Products and Services  Corporate Structure  Technologies Site Map Contact us

                      COMLEC PTE LTD    The SkyTech. Blk 2 #05-11 Bukit Batok Street 24. Singapore 659480  Tel:65-67415738  Fax:65-67444696  

                                                                       Email: comlec@pacific.net.sg  or  sales@comlec.com

                        ©copyright 2001~2009 Comlec Pte Ltd. All rights reserved. Disclaimer                        updated 25 Apr 2010