Application
The relay type NA11 can be used in radial networks as feeder
or power transformer protection.
In solidly grounded systems the residual overcurrent
protection can be used on feeders of any lenght, while in
ungrounded or Petersen coil and/or resistance grounded
systems, the residual overcurrent protection can be used on
feeders of small lenght in order to avoid unwanted trippings
due to the capacitive current contribution of the feeder on
external ground fault.
Beside to the phase and residual overcurrent protections, the
automatic reclosing function is provided.
Protective
functions
50/51 - Phase overcurrent
50N/51N - Earth fault
79 - Automatic reclosure
BF - Circuit breaker failure
|
|
|
|
|